Contact us for a free site visit and estimate - (914) 740-5340
Contact us for a free site visit and estimate - (914) 740-5340
DC315 applied over Spray Polyurethane Foam (SPF), is an Alternative Barrier System in “Section 2603.9 Special Approval” as a thermal barrier.
To be approved as an Alternative Barrier System, DC315 is applied over a manufacturer’s SPF and tested to the criteria of an NFPA 286, UL 1715, UL 1040, or FM 4880 for duration of 15 minutes by an accredited fire testing facility.
Products that pass an ignition barrier tested under AC 377 Appendix X are not appropriate alternative thermal barriers and cannot be used. Depending on your particular application, either ignition or thermal barriers are required by the International Building Code (IBC).